What is the clearance for cooling of FrigoPack FEP?
Sizes B and C (up to 15 kW):
Top & bottom: 60 mm, front: 15 mm, left & right: 15 mm
Size D (up to 30 kW):
Top & bottom: 60 mm, front: 25 mm, left & right: 15 mm
Sizes E and F (up to 90 kW):
Top & bottom: 60 mm, front: 25 mm, left & right: 0 mm
Can I install FrigoPack outside an electrical enclosure?
Which types of pressure sensors or transmitters are to be used?
×
Print
Which types of pressure sensors or transmitters are to be used?
FrigoPack Frequency Inverters are only to be used with HUBA control pressure sensors or transmitters. Other makes and types of sensors must not be used. Please refer to "Products/Accessories FrigoPack" for information on permissible types.